6.Rated output current (or rated output capacity)
Indicates the rated output current of the inverter within the specified load power factor range. Some inverter products give a rated output capacity, the unit of which is expressed in VA or kVA. The rated capacity of the inverter is the product of the rated output voltage as the rated output current when the output power factor is 1 (ie, purely resistive load).
7.Safeguard
An inverter with excellent performance should also have complete protection functions or measures to deal with various abnormal conditions that occur during actual use, so that the inverter itself and other components of the system are protected from damage.
1) Input undervoltage protector
When the input voltage is lower than 85% of the rated voltage, the inverter should be protected and displayed.
2) Input overvoltage policy
When the input voltage is higher than 130% of the rated voltage, the inverter should be protected and displayed.
3) Overcurrent protection:
The overcurrent protection of the inverter should ensure that the load acts in a timely manner when the load is short-circuited or the current exceeds the allowable value, so as to protect it from inrush current. When the operating current exceeds 150% of the rated value, the inverter should be automatically protected.
4) Output short-circuit policy
The inverter short-circuit protection action time should not exceed 0.5s.
5) Input reverse connection protection
When the positive and negative terminals of the input are reversed, the inverter should have protection function and display.
6) Lightning protection
The inverter should have lightning protection.
7) Over temperature protection, etc.
In addition, for inverters without voltage stability measures, the inverter should also have output overvoltage protection measures to protect the load from overvoltage.
8. Starting characteristics
Characterizes the ability of the inverter to load start and performance during dynamic operation. The inverter should be guaranteed to start reliably under rated load.
9. Noise
Transformers, filter inductors, electromagnetic switches, and fans in power electronics can generate noise. When the inverter is in normal operation, the noise should not exceed 80dB, and the noise of the small inverter should not exceed 65dB.
Previous: PV inverter selection skills
Next: The Main Technical Indicators of Photovoltaic Inverters 1
Related Industry Knowledge
- Effect of the inverter and the moto...
- Installation and maintenance of the...
- Misunderstandings and Countermeasur...
- Inverter control cabinet profile an...
- Inverter Installation Requirements
- Four motor drive control
- Development drive: energy-saving an...
- Domestic drive in the drive to defe...
- Electronic Energy Meter advantage c...
- Drive higher harmonics are you afra...
- PV inverter selection skills
- How to reduce the UPS power battery...
- Steady-state and dynamic test metho...
- Talking about the Importance of UPS...
- Off Grid Pure Sine Wave Inverter
- 3-5KW solar grid tie inverter
- Inverter With Pure Sine Wave
- Energy saving and environmental pro...
- Mistake analysis of frequency conve...
- How to deal with the crash of the i...